l The magnetic valves that control the flow of
DETECTING AND CORRECTING
refrigerant
PROBLEMS
l The wiring system that connects the sensing
A number of symptoms indicate faulty operation of
elements to the solenoids of the magnetic valves
refrigeration and air-conditioning plants. Figures 5-7,
and the controller of the electric heaters
5-8, and 5-9 list some of the problems along with
Trouble
High condensing pressure.
Possible Cause
Corrective Measure
Air on noncondensable gas in system.
Purge air from condenser
Inlet water warm.
Increase quantity of condensing water.
Insufficient water flowing through
Increase quantity of water.
condenser.
Condenser tubes clogged or scaled.
Too much liquid in receiver,
condenser tubes submerged in liquid
refrigerant.
Clean condenser water tubes.
Draw off liquid into service cylinder.
Low condensing pressure.
Too much water flowing through
condenser.
Reduce quantity of water.
High suction pressure.
Water too cold.
Reduce quantity of water.
Liquid refrigerant flooding back from
Change expansion valve adjustment,
evaporator.
examine fastening of thermal bulb.
Leaky discharge valve.
Remove head, examine valves.
Replace any found defective.
Overfeeding of expansion valve.
Regulate expansion valve, check bulb
attachment.
Low suction pressure.
Leaky suction valve.
Restricted liquid line and expansion
valve or suction screens.
Insufficient refrigerant in system.
Too much oil circulating in system.
Remove head, examine valve and
replace if worn.
Rump down, remove, examine and
clean screens,
Check for refrigerant storage.
Check for too much oil in circulation.
Remove oil.
Improper adjustment of expansion
valves.
Adjust valve to give more flow.
Expansion valve power element dead
Replace expansion valve power
or weak
element.
Figure 5-7.Trouble diagnosis chart.
5-13
