CHAPTER 5
REFRIGERATION AND AIR CONDITIONING
As an EN3, you have learned the principles of
refrigeration and air conditioning; the components and
accessories that make up the system; and how to start,
operate, and secure refrigeration and air-conditioning
plants. As an EN2, you will perform routine
maintenance jobs, such as cleaning, lubricating,
troubleshooting, servicing the system, using correct
procedures for leak detecting, and charging the
refrigeration and air-conditioning plants. As you
advance in rate, you will be expected to have a greater
knowledge of the construction and operating principles
of refrigeration and air-conditioning plants. You will be
required to perform more complicated maintenance
jobs, to make repairs as required, and to determine the
causes of inefficient plant operation and accomplish the
necessary corrective procedures. This chapter provides
some general information on the construction and
maintenance of refrigeration and air-conditioning
equipment and the detection and correction of operating
difficulties.
Refer to the manufacturers technical manual for
details of the plant on your ship. If you have any
questions about the basic theory of refrigeration and air
conditioning, refer to EN3, chapters 16 and 17.
R-12 REFRIGERATION SYSTEM
We will present the R-12 system as though it had
only one evaporator, one compressor, and one
condenser. A refrigeration system may (and usually
does) include more than one evaporator, and it may
include an additional compressor and condenser units.
COMPRESSORS
Many different types and sizes of compressors are
used in refrigeration and air-conditioning systems. They
vary from the small hermetic units used in drinking
fountains and refrigerators to the large centrifugal units
used for air conditioning.
One of the most common compressors on modem
ships is a high-speed unit with a variable capacity. This
compressor is a multicylinder, reciprocating design with
an automatic device built into the compressor to control
its output. This automatic capacity control provides for
continuous compressor operation under normal load
conditions. The capacity of the compressor is controlled
by unloading and loading the cylinders. This is a very
desirable design feature of the unit. If the compressor
had to be started under a load, or with all cylinders
working, a much greater amount of torque would be
required, and it would be necessary to have a much
larger drive motor. Also, if the compressor ran at
constant capacity or output, it would reach the
low-temperature or low-pressure limits or be constantly
starting and stopping, thereby putting excessive work on
the unit.
Unloading of the cylinders in the compressor is
accomplished by lifting the suction valves off their seats
and holding them open. This method of capacity control
unloads the cylinders completely but still allows the
compressor to work at as little as 25 percent of its rated
capacity .
Unloader Mechanism
When the compressor is not in operation, the
unloader mechanism is in the unloaded position as
shown in figure 5-1. The mechanism is operated by oil
pressure from the capacity control valve. The oil
pressure pushes the unloader spring against the unloader
piston. This action moves the unloader rod to the left,
thereby rotating the cam rings. As the cam rings are
rotated, the lifting pins are forced upward, raising the
suction valve off its seat. The suction valve is held in
this position until the compressor is started and oil
pressure of approximately 30 psi is reached. At that time,
the oil pressure from the capacity control valve pushes
the unloader piston back to the right against the unloader
spring. The motion transmitted through the pushrod
rotates the cam ring. This lowers the lifting pins and
allows the suction valve to close or operate normally and
the cylinder to become loaded (fig. 5-2). On most
compressors the unloader is connected to the cylinders
in pairs.
Capacity Control Valve
The capacity control valve (fig. 5-3) is located in the
compressor crankcase cover. The valve is actuated by
oil pressure from the main oil pump. It admits or relieves
oil to or from the individual unloader power elements,
5-1
